Table of data
Name HIS 71
Supply voltage (Un) 230V AC, +10%, -15%
Babysitting voltage network (Uit) 0-275V / 50Hz
Consumption, (P) max. 2.6 VA
Measuring voltage from the internal source (Um) 24V DC
Measuring current (Im) <1 mA
Measuring internal impedance input (Rv) > 3MOhm (4.6 M at 230 V AC)
Guarded insulation resistance (RCRIT) 10 to 210 Ohm
Hysteresis (H) 25% of the set value
Katagoria surge III.
Degree of pollution 2
El. strength against internal power supply wires 3.7 kVefef
Vibration according to IEC 654-3, N2 10 - 55Hz displacement amplitude of 0.35 mm
CMOS contact: max. switching current 20 mA
CMOS contact: max. switching voltage 30V DC
The values of the internal source of external power supply 12V DC / 20 mA
Recommended back-up fuse, (A) 30 mA
Connection cross section (solid / flexible), (mm2) 1
Terminal remote signaling (mm2) 1
Operating temperature, (J) -25 To +55 ° C
Dimensions in mm (LxWxH) 35,2 x67x90
Number of modules (TE (17.5)) 2
Degree of protection (IP) IP 20
Environment basic
The method of installation DIN rail 35mm
Material of housing SLOVAMID 6FRC2
Mass (m) 250 g
EAN code 700716
Packaging 1

 

HIS 71 
HIS 71 

The device continuously monitors the resistance HIS isolated IT-networks against PE conductor, ev. to ground. When the insulation resistance drops below the set value R CRIT relay switches at the output and at the same time informs the detector optically switching two-color LED on the front panel in red. In normal operation, the resistance of isolated networks against protective conductor PE is higher than the set value R CRIT , the indicator is green. Setting the value of RCRIT is set by knob potentiometer located on the front panel. 
Leakage state is built into a plastic box about the size of two modules (2TE) and is designed for mounting on DIN rail 35 mm.

 
 
 
 
Type HIS 71
Power supply (+10% -15%) 
N 
230 
In AC 
Voltage secure IT network 
ForIT 
0-275 
In AC 
Consumption 
max 2.6 
VA 
Measuring voltage 
M 
24 
DC 
Measuring current 
M 
<1 
mA 
Critical insulation resistance 
RCRIT 
10:210 

 